Difference between revisions of "UPS Handling with NUT"

From Da Nerd Mage Wiki
Jump to navigation Jump to search
Line 43: Line 43:


* <code>sudo vi /etc/nut/upsd.users</code>
* <code>sudo vi /etc/nut/upsd.users</code>
[upsmon]
        password = supersecretpassword
        upsmon master
* <code>sudo vi /etc/nut/upsmon.conf</code>
* <code>sudo vi /etc/nut/upsmon.conf</code>
MONITOR myups@192.168.2.219 1 monuser supersecretpassword master


= Manage NUT =
= Manage NUT =

Revision as of 19:06, 3 February 2022

Proven on:
Logo Debian.png
11 (bullseye)
As always...

Start with:

  • sudo apt update
  • sudo apt upgrade

Install NUT

  • sudo apt install nut

Configure NUT

  • sudo vi /etc/nut/nut.conf
MODE=netserver
  • sudo vi /etc/nut/ups.conf
[cyberpower]
       driver = usbhid-ups
       port = auto
  • sudo upsdrvctl start
  • ip a
  • sudo vi /etc/nut/upsd.conf
LISTEN 192.168.2.219
LISTEN 127.0.0.1 3493
LISTEN ::1 3493
  • sudo vi /etc/nut/upsd.users
[upsmon]
       password = supersecretpassword
       upsmon master
  • sudo vi /etc/nut/upsmon.conf
MONITOR myups@192.168.2.219 1 monuser supersecretpassword master

Manage NUT

  • sudo service nut-server restart
  • sudo service nut-server status
  • upsc cyberpower
  • upscmd -l cyberpower