Difference between revisions of "UPS Handling with NUT"
Jump to navigation
Jump to search
| Line 43: | Line 43: | ||
* <code>sudo vi /etc/nut/upsd.users</code> | * <code>sudo vi /etc/nut/upsd.users</code> | ||
[upsmon] | |||
password = supersecretpassword | |||
upsmon master | |||
* <code>sudo vi /etc/nut/upsmon.conf</code> | * <code>sudo vi /etc/nut/upsmon.conf</code> | ||
MONITOR myups@192.168.2.219 1 monuser supersecretpassword master | |||
= Manage NUT = | = Manage NUT = | ||
Revision as of 19:06, 3 February 2022
| 11 (bullseye) |
| As always... | |
|---|---|
|
Start with: |
|
Install NUT
sudo apt install nut
Configure NUT
sudo vi /etc/nut/nut.conf
MODE=netserver
sudo vi /etc/nut/ups.conf
[cyberpower]
driver = usbhid-ups
port = auto
sudo upsdrvctl startip asudo vi /etc/nut/upsd.conf
LISTEN 192.168.2.219 LISTEN 127.0.0.1 3493 LISTEN ::1 3493
sudo vi /etc/nut/upsd.users
[upsmon]
password = supersecretpassword
upsmon master
sudo vi /etc/nut/upsmon.conf
MONITOR myups@192.168.2.219 1 monuser supersecretpassword master
Manage NUT
sudo service nut-server restartsudo service nut-server status
upsc cyberpowerupscmd -l cyberpower